6  Setting

S

et

R

eset

1:  locking ring

2:  setting rings 

3:  LED green: supply voltage

4:  setting marks

5:  LED yellow:  

Temperature ≥ SET;  

OUT1 closed / OUT2 open

6:  process connection

 

► Turn the locking ring to the unlocked position.

 

► Turn both setting rings to the lowest setting. 

This is important to ensure the setting accuracy.

 

► Rotate SET ring to desired temperature.

 

► Rotate RESET ring to desired temperature. 

The RESET value must be lower than the SET value. 

Minimum distance between SET and RESET = 3 K (= hysteresis).

 

► Turn the locking ring to the locked position.