• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator�
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator�
• Protect units and cables against damage�
3 Getting started
The unit can be used without any further parameter setting with the settings
If necessary, the factory setting can be changed via the IO-Link interface:
►
Connect unit to PC to set the parameters via the IO-Link interface�
►
Set the standard unit of measurement�
-[Uni]: °C or °F
►
Set the analogue signal�
-[OU2]: I = 4���20 mA or Ineg = 20���4 mA or OFF = output off
-[ASP] and [AEP]: Scaling of the measuring range�
►
Configure the analogue signal for the alarm�
-[FOU2]: On = 21�5 mA or OFF = 3�5 mA
►
Set the calibration check limit�
-[ccL]: Temperature deviation from which the unit provides a warning�
►
Configure the switching logic for the alarm and the warning of the diagnostic
output�
-[P-n]: PnP or nPn
►
Activate / deactivate the LED at the head of the unit�
-[LED]: ON = LED is on (green, blue, red) or OFF = LED off or Notification =
LED on for warnings and alarms only
►
Finish parameter setting, install
4 Functions and features
The unit detects the medium temperature and provides the measured value via an
analogue and/or a digital signal�