SmartPLC DataLine with EtherNet/IP device interface
40
>
5.3.2
Quick setup: Configure the operating mode of the AS-i masters
41778
Information regarding the operating modes of an AS-i master:
→
Operating modes of the AS-i
master
(
To configure the operating modes of the AS-i masters:
1 Select the menu page
►
►
Select [Operation modes] tab.
2 Configure the operating mode of AS-i master 1 and the behaviour of the connected AS-i slaves
>
In group [AS-i master 1], set the following parameters as required:
Parameter
Description
Possible values
[Projection mode]
Active operating mode of the
AS-i master
Projection mode inactive:
AS-i network runs in protected mode (normal mode)
Projection mode active:
AS-i network can be projected.
(
→
Quick setup: Address the AS-i slaves connected to AS-i
Master 1
(
→ S.
) or
→
Quick setup: Address the AS-i slaves
connected to AS-i Master 2
(
→ S.
[No slave reset]
Behaviour of the AS-i slaves
when changing the operating
mode
Slave is reset when changing the operating mode:
When changing the operating mode, the AS-i slaves will
be reset for a short moment (reset or offline phase).
Slave is not reset when changing the operating mode:
When changing the operating mode, the AS-i slaves
continue to operate without interruption.
>
Selected values are applied.
3 Optional: set the operating mode of AS-i master 2 and the behaviour of the AS-i slaves
►
Repeat step 2 for the group [AS-i master 2].