SmartPLC DataLine with EtherNet/IP device interface
197
>
8.8.2
OSC messages: AS-i 1 / AS-i 2
41735
Message
Type
Corrective measures
System errors: AS-i master <1,2>
Error
► Reboot the device
If the error occurs again:
► Note the message and contact the ifm service center!
Earth fault: AS-i <1,2>
Error
► Check for earth fault of AC1423/24
Incorrect profile: AS-i <1,2>, slave <1(A)..31(A),
1B..31B> with profile <S-x.x.x> expected, but
<S-y.y.y> found.
Error
► Check profile of the AS-i slave
Config error: AS-i <1,2>, slave <1(A)..31(A),
1B..31B> with the profile <S-x.x.x> missing
Error
► Check connections of the AS-i slave
► Reconnect AS-i slave
Config error: AS-i <1,2>, slave <1(A)..31(A),
1B..31B> with the profile <S-x.x.x> is available
but not projected
Error
► Carry out projection process
([Quick setup] > [Project all])
Protocol error: AS-i <1, 2>, slave <1(A)..31(A),
1B..31B> no data transmission
Error
► Improve the transmission quality on the AS-i line
Double address detected: AS-i <1, 2>, slave
<1(A)..31(A), 1B..31B>
Error
► Remove an AS-i slave with a double address from the AS-i
network
► Readdress the remaining AS-i slave
► Reconnect removed AS-i slave to the AS-i network
The automatic addressing is not activated for
AS-i <1,2>.
Warning
► Activate automatic addressing
([AS-i1]/[AS-i2] > [Master setup])
A voltage drop of 19.0 V was detected on AS-i
master <1,2>
Warning
► Check voltage supply of the device and replace if
necessary
A voltage drop of 22.5 V was detected on AS-i
master <1,2>
Warning
► Check voltage supply of the device and replace if
necessary
Increased message error rate: AS-i <1, 2>, slave
<1(A)..31(A), 1B..31B>
Warning
► Improve the transmission quality on the AS-i line
Peripheral fault: AS-i <1, 2>, slave <1(A)..31(A),
1B..31B>
Warning
► Check displayed AS-i slave
AS-i slave with address 0 cannot be
automatically readdressed (wrong profile)
Warning
► Activate automatic addressing
([AS-i1]/[AS-i2] > [Master setup]
Manual output change: AS-i <1, 2>, slave
<1(A)..31(A), 1B..31B>, value: <0..F, 0..32768>
Event
not necessary
Manual parameter change: AS-i <1, 2>, slave
<1(A)..31(A), 1B..31B>, value: <0..F, 0..32768>
Event
not necessary
AS-i master <1,2> was switched to the
<geschützten Betrieb,Projektierungsmodus>
Event
not necessary
AS-i projection process was carried out.
Event
not necessary
AS-i slave with the address 0 was detected
Event
not necessary