SmartPLC DataLine with EtherNet/IP device interface
140
>
8.7.3
Device-specific parameters
Content
Parameters: Independent mode ...........................................................................................................140
Parameters: Top-down mode ...............................................................................................................141
Parameter setting via the configuration assembly object .....................................................................143
EDS-file.................................................................................................................................................159
41583
The device-specific parameters allow you to make individual adjustments to the system. Depending on
the selected configuration mode, the following parameters are available.
>
Parameters: Independent mode
41806
Parameter
Description
Value range
Analogue channels per input slave
Number of analogue channels
per input slave
4 channels*
4 channels
(variable slave assignment)
2 channels
2 channels
(fixed slave assignment)
1 channel
1 channel
(fixed slave assignment)
1 channel per
A/B slave
1 channel per A/B slave
(fixed slave assignment)
Analogue channels per output slave
Number of analogue channels
per output slave
4 channels*
4 channels
(variable slave assignment)
2 channels
2 channels
(fixed slave assignment)
1 channel
1 channel
(fixed slave assignment)
1 channel per
A/B slave
1 channel per A/B slave
(fixed slave assignment)
Fail-safe state
Behaviour of the slave outputs if
an interrupted fieldbus
connection is detected
Reset
outputs*
All AS-i outputs are switched off in
case of an interrupted EtherNet/IP
connection (value = 0).
Hold outputs
The outputs are held in the last
valid state that existed before the
interrupted connection was
detected.
Change byte order
Byte order in a word
Setting applies to all data of
object class 4, instances 100
and 150
Disabled*
Byte order in word remains
unchanged.
Enabled
Byte order in word is inverted.
* ... Default setting
In the 'Independent' configuration mode, the device-specific parameters are configured via
the GUI of the device (
→
Configuration mode: Independent
(