Operating instructions 

Magnetic-inductive  

flow meter

SM9x04 

SM2x04

80223777 / 00    05 / 2016

UK

Summary of Contents for SM9x04 Series

Page 1: ...Operating instructions Magnetic inductive flow meter SM9x04 SM2x04 80223777 00 05 2016 UK...

Page 2: ...value damping dAP 9 4 7 Low flow cut off LFC 9 4 8 Simulation 9 4 9 IO Link 9 5 Installation 10 5 1 Recommended installation locations 10 5 2 Not recommended installation position 11 5 3 Grounding 12...

Page 3: ...ng 25 10 4 6 Setting of the error behaviour of the outputs 25 10 4 7 Activating deactivating empty pipe detection 26 10 4 8 Time delay empty pipe detection 26 10 4 9 Setting of the empty pipe detectio...

Page 4: ...operty can occur Improper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connec tion set up operation and main...

Page 5: ...otective cover Do not press the pushbuttons manually instead use another object e g ballpoint pen This is a class A product This unit may cause radio interference in domestic areas If required take ap...

Page 6: ...on to the flow velocity and the volumetric flow quantity the unit also de tects the direction of flow 4 2 1 Determination of the direction of flow Fdir An arrow with the text flow direction on the uni...

Page 7: ...activated 10 4 7 If it is active and the pipe is empty the unit reacts as follows SEnS is indicated in the display The flow is set to zero The empty pipe detection can be set as time depending or not...

Page 8: ...UL OL cr OL Figure 1 Characteristics of the analogue output according to the standard IEC 60947 5 7 Q Flow a negative flow value means flow against the marked flow direction T Temperature UL Below the...

Page 9: ...n Low Flow cut off small volumetric flow quantities can be ignored 10 4 10 Flows below the LFC value are evaluated by the sensor as standstill Q 0 4 8 Simulation With this function flow and temperatur...

Page 10: ...ly filled 5 1 Recommended installation locations Example of an optimised installation F 1 Install the unit so that the measuring pipe is completely filled Arrange for inlet and outlet pipe lengths Dis...

Page 11: ...e 3 F F 4 F F flow direction With empty pipe detection Install the unit according to figure 1 or 3 5 2 Not recommended installation position Avoid the following installation positions F F F Directly i...

Page 12: ...f the spout of the pipe F On the suction side of a pump F flow direction 5 3 Grounding If installed in an ungrounded pipe system e g plastic pipes the unit must be grounded functional earth Ground bra...

Page 13: ...rked flow direction To mount the adapters on the process connection of the sensor use suitable lubricants 3 Screw the adapter B with the threads D until it is hand tight 4 Tighten the two adapters in...

Page 14: ...must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows 4 3 2 1 BK black BN brown BU blue WH white L L OUT1 OUT2 4 2 4 2 1 3 Colours to DIN EN 60...

Page 15: ...with setting SELd TEMP Parameters and parameter values 10 Enter button Selection of the parameters Reading of the set values Confirmation of the parameter values Representation in 8 Menu 11 Buttons u...

Page 16: ...16 8 2 Main menu Extended functions Process value display EF 8 3 8 4 8 4 8 4 8 3 Basic settings 8 4 Min max memory Empty pipe Simulation...

Page 17: ...e start value for volumetric flow AEP2 Analogue end value for volumetric flow EF Extended functions opening of menu level 2 Explanation extended functions EF rES Restore factory setting IO L Activate...

Page 18: ...18 8 3 Basic settings Main menu CFG EF...

Page 19: ...Measured value damping damping constant in seconds diS Update rate and orientation of the display Uni F Standard unit of measurement for volumetric flow Uni T Standard unit of measurement for tempera...

Page 20: ...20 8 4 Min max memory Empty pipe Simulation Main menu EF MEM SIM 8 1 EPD Parameters are only displayed for the selection EP On On...

Page 21: ...ion flow value S TMP Simulation temperature value S Tim Simulation time S On Simulation start 9 Set up After power on and expiry of the power on delay time approx 5 seconds the unit is in the normal o...

Page 22: ...there will be no malfunctions in your plant During parameter setting the unit remains in the operating mode It continues to monitor with the existing parameter until the parameter setting has been com...

Page 23: ...4 5 3 Confirm the parameter value 6 Press Enter briefly The parameter is displayed again The new setting value is saved 6 Finish parameter setting and change to the process value display Wait for 30...

Page 24: ...ke sure that the unit is in the normal operating mode Press and simultaneously for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Unlocking Press...

Page 25: ...e of the measured values every 600 ms rd1 rd2 rd3 display as for d1 d2 d3 rotated by 180 OFF the display is switched off in the operating mode 10 4 4 Changing the direction of the flow rate measuremen...

Page 26: ...l 10 4 9 Setting of the empty pipe detection Select EP Pr to display the current value of the empty pipe detection in percent Select EP SP and set the switch point of empty pipe detection 10 4 10 Sett...

Page 27: ...S On and set the function On The simulation starts The values are simulated for the time set at S Tim SIM is displayed simultaneously with the process values Cancel with Enter OFF The simulation is n...

Page 28: ...ther process values can be read in addition to the preset standard display Press the buttons or The LED of the selected process value display is lit and the current process value is displayed After 30...

Page 29: ...oubleshooting The unit has many self diagnostic options It monitors itself automatically during operation Warnings and error states are displayed even when the display is switched off Error indication...

Page 30: ...aram eter setting software UL Warning Below the display range Current value between 130 120 MEW Temperature value between 50 40 C or 58 40 F Check flow range temperature range cr UL Error Below the de...

Page 31: ...AEP1 TEMP 80 C IO L OFF FDir FOU1 OFF FOU2 OFF dAP 0 6 s diS d2 Uni F SMx004 l min SMx604 gpm Uni T SMx004 C SMx604 F SELd FLOW LFC 5 l min EP On OFF dEP E 0 s dEP F 2 s EP SP 75 S FLW 20 S TMP 20 C...