7
UK
Q:
Flow (a negative flow value means flow against the marked flow direction)
T:
Temperature
UL:
Below the display range
OL:
Above the display range
Err:
The unit is in the error state
FOU=On: Default setting at which the analogue signal goes to the upper final value in
case of an error�
FOU=OFF: Default setting at which the analogue signal goes to the lower final value in
case of an error�
1
Analogue signal
2
Measured value (flow or temperature)
3
Detection zone
4
Display range
5
Measuring range
5*
Analogue signal in the measuring range
with factory setting
6
Scaled measuring range
6*
Analogue signal for scaled measuring
range
4.4 Measured value damping (dAP)
The damping time allows to set after how many seconds the output signal has
reached 63 % of the final value if the flow value changes suddenly� The set damp-
ing time stabilises the outputs and the display� The signals [UL] and [OL]
are defined under consideration of the damping time�