Summary of Contents for SI0558

Page 1: ...Operating instructions Flow monitor SI0558 SI0564 11441063 00 03 2022 GB...

Page 2: ...position 6 4 1 3 Conditionally possible installation position 6 4 1 4 Impermissible installation position 7 4 2 Interference 7 4 3 Process connection 7 5 Electrical connection 9 6 Operating and displa...

Page 3: ...e unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malf...

Page 4: ...ad this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restr...

Page 5: ...based on the calorimetric measuring principle and switches the output The switch point is adjustable The typical response time of the device is 1 10 s It can be influenced by the setting of the switch...

Page 6: ...Immersion depth 12 mm Fig 1 Immersion depth The sensor tip must be completely surrounded by the medium Recommended immersion depths minimum 12 mm 4 1 2 Recommended mounting position Fig 2 Recommended...

Page 7: ...e adapted to different process connections A correct fit of the unit and ingress resistance of the connection are only ensured using ifm adapters For small flow rates ifm adapter blocks are available...

Page 8: ...SI0558 SI0564 Flow monitor 8 u Place the flow monitor onto the adapter and tighten the nut Tightening torque 25 Nm Ensure that the unit is correctly oriented...

Page 9: ...electrical equipment u For the output circuit take the same protective measures as for the supply circuit u Insert a miniature fuse according to IEC 60127 2 Sheet 1 5 A fast acting u Disconnect power...

Page 10: ...SP 1 Operation indication The LEDs 0 9 represent the range of the monitored flow The green LEDs show the current flow An illuminated LED shows the position of the switching point Orange output closed...

Page 11: ...Flow monitor SI0558 SI0564 11 7 Set up u Switch on the supply voltage w All LEDs light and go out again step by step During this time the output is closed w The device is in the operating mode...

Page 12: ...quired switch point is reached do not press the button for more than 2 seconds w The device goes into operating mode with the newly set value 8 2 Teaching the switch point The switch point can be set...

Page 13: ...Flow monitor SI0558 SI0564 13 u Press both setting keys for 10 seconds w The display goes off w The unit is locked u For unlocking repeat the process...

Page 14: ...w switch point Output open LED red if volumetric flow quantity switch point In case of power failure or interruption of the operating voltage all settings remain Operating indicators Explanation Curre...

Page 15: ...ly locked After approx 0 6 seconds the last oper ating status is indicated u Unlock unit See Lock unlock 12 Display OFF no LED on Operating voltage too low 19 V or failed u Ensure correct voltage supp...

Page 16: ...or tip for build up one month after set up Repeat check regularly Determine check intervals based on the application In case of soiling clean the sensor tip with a soft cloth Stubborn build up such as...