background image

Mechatronic flow sensor

SBx4xx

7

5 Mounting

CAUTION

During installation or in case of a fault (e.g. housing damage) media under high pressure or
hot media can leak from the system.

w

Risk of injury caused by pressure or burns.

u

Ensure that the system is free of pressure during installation.

u

Ensure that no media can leak at the mounting location during installation.

u

Equip the unit with suitable protection (e.g. cover) to avoid hazard to personnel from
leaking media.

5.1 Process connection

u

Avoid major changes of cross section on the inlet side.

u

Fit the unit in the pipe in accordance with the flow direction (arrow) and tighten at the spanner flats.

Do not clamp the housing in a vice.

IN

OUT

1

Fig. 2: Process connection

IN:

Inlet

OUT:

Outlet

Loosening the socket head screw (1) and moving the cap do not change the setting of the
sensor. However, moving the cap may be useful to read the label.

Calming sections on the sensor's inlet or outlet side are not necessary.

The sensor can also prevent backflow.

5.2 Interference

u

The following minimum distances must be adhered to:

Distance between the sensor and ferromagnetic materials

≥ 30 mm *

Distance between the sensor and constant / alternating fields

≥ 500 mm

Distance between the sensor axes for side-by-side installation

≥ 50 mm

* The pipe may consist of ferromagnetic material.

GB

Summary of Contents for SB4 Series

Page 1: ...Operating instructions Mechatronic flow sensor SBx4xx 11368300 00 05 2021 GB...

Page 2: ...instructions 4 3 Intended use 5 4 Function 6 4 1 Analogue output 6 5 Mounting 7 5 1 Process connection 7 5 2 Interference 7 5 3 Mounting accessories 8 5 4 Installation in case of water containing dirt...

Page 3: ...at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interfere...

Page 4: ...Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any res...

Page 5: ...ns industrial oils coolants It detects the volume flow flow rate time and outputs an analogue signal that is proportional to the process value ATTENTION Frost formation of the medium w The sensor may...

Page 6: ...f a permanent magnet and a measuring cell 4 1 Analogue output I mA 20 4 0 MEW Q l min 0 Fig 1 Analogue output water 20 C The analogue signal for water is linear from 4 mA no flow to 20 mA final value...

Page 7: ...it in the pipe in accordance with the flow direction arrow and tighten at the spanner flats Do not clamp the housing in a vice IN OUT 1 Fig 2 Process connection IN Inlet OUT Outlet Loosening the socke...

Page 8: ...side of the unit Information about available accessories at www ifm com 5 4 Installation in case of water containing dirt u Use a 200 micron filter in front of the inlet IN u Install sensor horizontal...

Page 9: ...ernational regulations for the installation of electrical equipment Voltage supply according to EN 50178 SELV PELV u Disconnect power u Connect the unit as follows 4 3 2 1 L L 1 BN 2 WH 3 BU Fig 5 Wir...

Page 10: ...re are dirt particles between the float and the housing the display value of the sensor does not return to zero in case of flow standstill In case of contamination the display value can be up to 30 of...

Page 11: ...Remove float and spring u Clean the inside of the float spring and housing e g by means of compressed air u Before re assembly check O ring for damage If necessary replace and grease u After cleaning...

Reviews: