8.2 Explanation of the menu
SP1/rP1
Upper / lower limit value for system pressure at which OUT1 switches�
OU1
Output function for OUT1:
Switching signal for the pressure limit values: hysteresis function [H ��] or
window function [F ��], either normally open [� no] or normally closed [� nc]�
EF
Extended functions / opening of menu level 2�
HI / LO
Maximum / minimum value memory for system pressure�
COF
Zero-point calibration�
CAr
Reset of the zero-point calibration�
dS1 / dr1
Switch-on delay / switch-off delay for OUT1�
dAP
Damping for OUT1�
diS
Update rate and orientation of the display�
Uni
Standard unit of measurement for system pressure�
9 Parameter setting
During parameter setting, the unit remains in the operating mode� It continues
to monitor with the existing parameters until the parameter setting has been
completed�
9.1 Parameter setting in general
3 steps must be taken for each parameter setting:
1
Parameter selection
►
Press [Mode/Enter] until the
requested parameter is displayed
.
Mode/Enter Set
2
Setting of the parameter value
►
Press [Set] and keep it pressed�
> Current setting value of the
parameter flashes for 5 s�
> After 5 s: Setting value is changed:
incrementally by pressing the button
once or continuously by keeping the
button pressed�
Mode/Enter Set
Numerical values are incremented continuously� To reduce the value: let the display
move to the maximum setting value� Then the cycle starts again at the minimum
setting value�