9.6.2 Read overload processes
• HIPC: number of overload processes
HIPC counts how often the limit HIPS has been exceeded�
The limit must be exceeded for at least 0�5 ms�
• HIPS: setting of the threshold for the overload counter�
The parameters HIPC and HIPS are only available via IO-Link
communication�
10 Operation
After power on, the unit is in the Run mode (= normal operating mode)� It carries
out its measurement and evaluation functions and provides output signals
according to the set parameters�
Operation indication
(→ 7 Operating and display elements)
�
10.1 Read set parameters
► Press [●].
► Press [▲] or [▼] until the requested parameter is displayed.
► Briefly press [●].
> The unit displays the corresponding parameter value for approx� 30 s; then it
changes to the process value display�
10.2 Self-diagnostics / fault indications
The unit has many self-diagnostic options�
• It monitors itself automatically during operation�
• Warnings and faults are displayed (even if the display is deactivated), in
addition they are available via IO-Link�
Display
Status LED
OUT1
Status LED
OUT2
Type of fault *
)
Fault / warning
Corrective measures
PARA
F Parameter setting outside
the permitted range�
►
Repeat parameter setting�
none
F Supply voltage too low�
►
Check / correct the supply
voltage�
SC
flashes
flashes flashes F Excessive current on
switching outputs OUT1
and OUT2 **
)
�
►
Check switching outputs for
short circuit or excessive
current; remove the fault�