12
•
Timeout:
If no button is pressed for 15 s during parameter setting, the unit returns to the
operating mode with unchanged values�
9.2 Configure display (optional)
►
Select [Uni] and set the unit of measurement:
[bar], [mbar], [MPa], [kPa], [PSI]�
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°�
-[OFF]: display switched off in the operating mode�
9.3 Set output signals
9.3.1 Set the output function
►
Select [OU1] and set the function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function/normally closed�
►
Select [OU2] and set the function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function/normally closed,
-[dESI] = output 2 used as a diagnostic output�
9.3.2 Set switching limits
►
Select [SP1] / [SP2] and set the value at which the output switches�
►
Select [rP1] / [rP2] and set the value at which the output switches back�
rPx is always smaller than SPx. The unit only accepts values which are
lower than the value for SPx�