3  Function and features

The pressure monitor detects the system pressure and switches the two 

complementary outputs OUT1 (pin 4) / OUT2 (pin 2):

•  In case of increasing pressure OUT1 closes / OUT2 opens when the set Set 

value is reached�

•  In case of decreasing pressure OUT1 opens / OUT2 closes when the set Reset 

value is reached�

Applications

Type of pressure: relative pressure

Order no.

Measuring range

Permissible 

overload pressure

Bursting

pressure

bar

MPa

bar

MPa

bar

MPa

PK6730

0���400

0���40

600

60

1 600

160

PK6731

0���250

0���25

400

40

1 000

100

PK6732

0���100

0���10

200

20

1 000

100

PK6734

0���10

0���1

25

2�5

300

30

Avoid static and dynamic overpressure exceeding the given overload

pressure�

Even if the bursting pressure is exceeded only for a short time the unit can 

be destroyed (danger of injuries)!

If the cable length exceeds 30 m or if used outside buildings, there is a risk 

of overvoltage pulses from external sources� We recommend to use the 

unit in protected operating environments and to limit overvoltage pulses to 

max� 500 V�

4  Installation

Before mounting and removing the sensor, make sure that no pressure is 

applied to the system�

5  Electrical connection

The unit must be connected by a suitably qualified electrician�

Voltage supply to EN50178, SELV, PELV�

 

Disconnect power before connecting the unit�

Summary of Contents for PK6730

Page 1: ...Operating Instructions Electronic pressure monitor PK673X 704878 00 03 2020 UK ...

Page 2: ...r indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note Contents 1 Preliminary note 2 1 1 Symbols used 2 2 Safety instructions 3 3 Function and features 4 4 Installation 4 5 Electrical connection 4 6 Setting Operation 5 ...

Page 3: ...product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features Only use the product for permissible media Technical data If the operating instructions or the technical data are not adhered to personal injury and or damage to ...

Page 4: ...00 0 10 200 20 1 000 100 PK6734 0 10 0 1 25 2 5 300 30 Avoid static and dynamic overpressure exceeding the given overload pressure Even if the bursting pressure is exceeded only for a short time the unit can be destroyed danger of injuries If the cable length exceeds 30 m or if used outside buildings there is a risk of overvoltage pulses from external sources We recommend to use the unit in protec...

Page 5: ... connection R A tightening torque 25 Nm 5 setting marks 6 yellow LED Set value reached OUT1 ON OUT2 OFF 7 internal thread M5 Minimum distance between Set and Reset 2 of the final value of the measuring range To obtain the setting accuracy Set the rings to the minimum value then set the requested value More information at www ifm com ...

Reviews: