CAN in the PDM360
CAN POUs to CANopen
254
Configuration of all correctly detected devices
8022
Every SDO is monitored for a response and repeated if the slave does not respond within the
monitoring time.
Automatic configuration of slaves
8023
Automatic configuration of slaves using SDOs while the bus is in operation:
Prerequisite: The slave logged in the master via a bootup message.
Start of all correctly configured slaves
8024
Start of all correctly configured slaves after the end of the configuration of the corresponding slave:
To start the slaves the NMT command "Start remote node" is normally used. As for the "reset" this
command can be replaced by "Start All Remote Nodes".
Start all nodes:
►
Call FB CANOPEN_NMTSERVICES (
→
):
- NODE = 0
- NMTSERVICE = 2
Cyclical transmission of the SYNC message
8025
This value can only be set during the configuration.
Nodeguarding with lifetime monitoring
8026
Setting of nodeguarding with lifetime monitoring for every slave possible:
The error status can be monitored via CANOPEN_GETGUARDHBERRLIST (
→
We recommend: It is better to work with the heartbeat function for current devices since then the bus
load is lower.
Heartbeat from the master to the slaves
8027
Heartbeat from the master to the slaves and monitoring of the heartbeats of the slaves:
The error status can be monitored via CANOPEN_GETGUARDHBERRLIST (
→
Reception of emergency messages
8028
Reception of emergency messages for every slave, the emergency messages received last are stored
separately for every slave:
The error messages can be read via CANOPEN_GETEMCYMESSAGES (
→
).