Photoelectric distance sensor
O1D110
9
6 Electrical connection
The unit must be connected by a qualified electrician.
u
Observe the national and international regulations for the installation of electrical equipment.
u
Voltage supply according to EN 50178, SELV, PELV.
u
Disconnect power.
u
Connect the unit as follows:
L
1 BN
5 GY
2 WH
4 BK
3 BU
IN1
L+
OUT2
2:
OUT1
4:
L
1 BN
5 GY
2 WH
4 BK
3 BU
IN1
L+
OUT2
2:
OUT1
4:
4
2
1
3
5
Fig. 2: Wiring diagram (colours to DIN EN 60947-5-2)
1 =
BN (brown)
2 =
WH (white)
3 =
BU (blue)
4 =
BK (black)
5 =
GY (grey)
6.1 Operation with IO-Link master
The unit is compatible with IO-Link master port class A (type A).
For operation with IO-Link master port class B (type B) observe the following:
As a standard, the unit is not compatible with master port class B (type B). Pin 2 [OU2] and pin
5 [IN1] are used for manufacturer-specific functions. That means that the main supply voltage of
the unit and the additional voltage supply (master port class B on pins 2/5) are not electrically
isolated.
With the following configurations the unit can be used with master port class B:
•
Connect unit and IO-Link master via 3 wires: Connect pins 1, 3 and 4 of the unit with the IO-Link
master (do not connect pins 2 and 5).
•
Connect unit and IO-Link master via 4 wires: Deactivate pin 2 (OU2) via IO-Link (setting OU2 =
"off") and connect pins 1, 2, 3 and 4 of the unit with the IO-Link master (do not connect pin 5).