O1D110
Photoelectric distance sensor
18
•
[Hnc] = hysteresis function / normally closed
•
[Fno] = window function / normally open
•
[Fnc] = window function / normally closed
•
[I] = current output analogue 4...20 mA:
•
[U] = voltage output analogue 0...10 V
u
Confirm with [MODE/ENTER].
10.2.9 Setting of the switch point for hysteresis function OUT2
u
Select [OU2], [Hno] or [Hnc].
u
Confirm with [MODE/ENTER].
u
Select [SP2] and set the switch point.
u
Confirm with [MODE/ENTER].
10.2.10 Setting of the switch points for window function OUT2
u
Select [OU2], [Fno] or [Fnc].
u
Confirm with [MODE/ENTER].
u
Select [nSP2] and set the switch point “near”.
u
Confirm with [MODE/ENTER].
u
Select [FSP2] nd set the switch point "far".
u
Confirm with [MODE/ENTER].
10.2.11 Scaling of the measuring range (analogue output)
u
Select [OU2], [I] or [U].
u
Confirm with [MODE/ENTER].
u
Select [ASP] and set the "Analogue start point". With [ASP]], you define at which measured value
the output signal is 4 mA / 0 V.
u
Confirm with [MODE/ENTER].
u
Select [AEP] and set the "Analogue end point". With [AEP]], you define at which measured value
the output signal is 20 mA / 10 V. It can also be selected so that it is located before [ASP]. This
implements a falling edge.
u
Confirm with [MODE/ENTER].
Minimum distance between [ASP] and [AEP]: 100 mm
When the minimum distance is not reached, the error message [SIZE] will be displayed.