The unit has the protection rating IP20 according to IEC/EN 60529.

u

Only install and use the unit under operating conditions that do not exceed
soiling degree 2 according to IEC EN 60664-1.
In case of use under operating conditions with a higher degree of soiling, the
unit must be protected accordingly.

u

Make sure all circuits connected with the unit comply at least with overvoltage
category II according to IEC EN 60664-1.

u

Only supplies providing protection against electrical shock (SELV or PELV)
may be connected to supply modules.

u

The installation regulations according to IEC/EN 60079-14 must be complied
with,

4.1 Requirements for cables and connection cables

u

The permissible wire cross section must be adhered to. In case multi-wire
conductors are used, they have to be crimped with wire end ferrules.

u

Make sure only one conductor per connecting terminal is used.

u

Make sure the insulation of the conductor reaches all the way to the connecting
terminal.

u

The tightening torque for the screws of the connecting terminal must be
adhered to.

If the voltage exceeds 50 V AC:

1. Switch off the voltage.

2. Attach or remove the terminal blocks.

4.2 Requirements in case of use as associated equipment

Circuits with Ex i type of protection that have been operated with non-intrinsically
safe circuits must no longer be used as circuits with Ex i type of protection then.

The intrinsically safe circuits of the associated equipment may be routed into
hazardous areas.

u

Make sure the separation distances to all non-intrinsically safe circuits
according to IEC/EN 60079-14 are observed.

u

Make sure the separation distances between two neighbouring intrinsically safe
circuits according to IEC/EN 60079-14 are observed.

GB

Summary of Contents for N0531A

Page 1: ...Operating instructions Switching amplifiers N0531A N0532A N0534A 80299362 00 02 2021 GB...

Page 2: ...3 2 ATEX certificate 4 3 3 IECEx certificate 4 3 4 Identification 4 4 Installation 4 4 1 Requirements for cables and connection cables 5 4 2 Requirements in case of use as associated equipment 5 5 Ele...

Page 3: ...the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are...

Page 4: ...ory 1G 2G apparatus for gas atmosphere The requirements of the standards EN IEC 60079 0 2018 EN 60079 11 2012 EN 60079 26 2007 Corr 2009 are met II 1 D group II category 1D apparatus for dust atmosphe...

Page 5: ...used they have to be crimped with wire end ferrules u Make sure only one conductor per connecting terminal is used u Make sure the insulation of the conductor reaches all the way to the connecting ter...

Page 6: ...the explosion protection according to IEC EN 60079 14 or IEC EN 60079 25 must be observed proof of intrinsic safety 5 Electrical connection NAMUR switch Mechanical switch Input circuit no 1 2 3 1 2 3...

Page 7: ...wire break or short circuit in the respective input circuit The corresponding output is not active transistor blocked relay de energised 3 LED green Lights when supply voltage is applied 4 Selector s...

Page 8: ...no 1 S3 must be in position I Without short circuit monitoring for input circuit no 2 and S3 in position I Without short circuit and wire monitoring for input circuit no 3 and S3 in position II 7 Mai...

Reviews: