11.2.1 Evaluate the index of the level edge
Index of level edge
Troubleshooting
• The substitute value
"255" is provided�
Reason: the measured
signal is too weak�
►
Increase the sensitivity of the sensor
►
Check the [Minimum recognition threshold] and reduce it
or reset it to factory setting
�
►
Reduce the wall thickness of the tank�
• The index of the level
edge maintains the
minimum value even
though the tank continues
to be filled�
►
Check the grounding and, if necessary, correct it
When used on a bypass pipe:
►
Insert the supply cable into the adapter�
• The index of the level
edge is in the measuring
range� However, the
position significantly
deviates from the actual
level�
►
Read the parameter [Signal strength]
�
Further procedure:
→ 11.2.2 Evaluate signal strength
11.2.2 Evaluate signal strength and filling edge sharpness
Parameter / value
Troubleshooting
Signal strength < 10
►
Reduce the wall thickness of the tank�
►
Increase the sensitivity of the sensor
►
Read parameter [Filling edge sharpness]
Filling edge sharpness
< 50
►
Install the unit where the edge of the level is at a right
angle to the active face�