![background image](http://html.mh-extra.com/html/ifm/efector-500-pp2001/efector-500-pp2001_operating-instructions-manual_620787012.webp)
12
10.3 Copying the parameter set of a sensor
1
►
Connect the sensor to PP2001
> The unit passes the initialisation
phase (→ 10.1) and then displays the
current measured value
2
►
Press [Mode/Enter] until [COPY] is
displayed
.
3
►
Press [Set] and keep it pressed
> [WAIT] flashes
►
Release [SET]
> [DONE] is briefly displayed The
copying process is finished and the
parameter set of the sensor is stored
in PP2001
4
►
Press [Mode/Enter] briefly
> The unit goes into the operation mode (the sensor type and then the current
measured value are displayed).
Error messages when carrying out the COPY action:
[ECOM] Input output error: communication error / data transfer disturbed
[EINI]
Communication error or data error; initialisation / support of the sensor not
possible
[ESEN] Sensor type error: the sensor type is not supported
[ESTO]
Error when storing the data set (e.g. B: data set too large).
The error message is displayed for 5 s Then the menu [COPY] is again active
In case of communication via IO-Link with a low baud rate the operation can take one minute
or more