After mounting, wiring and setting check whether the unit operates
correctly
Faults displayed during operation:
Adjustable parameters
27
ENGLISH
Technical information / Functioning / Parameters
Flashing: short circuit in the switching output 1*.
Flashing: short circuit in the switching output 2*.
Overload (above measuring range of the sensor).
Underload (below measuring range of the sensor).
Flashing: short circuit in both switching outputs*.
*The output concerned is switched off as long as the short circuit exists.
Installation and set-up / operation
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SP2 is active only if
OU2
=
Hno
,
Hnc
,
Fno
or
Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is auto-
matically reduced (rPx is set to the minimum setting value).
rP2 is active only if
OU2
=
Hno
,
Hnc
,
Fno
or
Fnc.
∆
P
max
min
max
min
SP1 / SP2
rP1 / rP2
0.1
99.5
-0.5
100
0.0
bar
10
1440
-10
1450
0
PSI
1)
0.01
9.95
-0.05
10.0
0.00
MPa
2)
1)
Measured value = displayed value * 10
2)
display
-.XX
=
-0.XX
∆
P
=
increments
Setting
range