background image

Bedienungsanleitung

Operating instructions

Notice utilisateurs

Elektronischer

Drucksensor

Electronic pressure

sensor

Capteur de pression

électronique

PF2652

R

DEUTSCH

ENGLISH

FRANÇAIS

Sachnr

. 701764/00     03/03

Summary of Contents for Efector 500 PF2652

Page 1: ...ienungsanleitung Operating instructions Notice utilisateurs Elektronischer Drucksensor Electronic pressure sensor Capteur de pression lectronique PF2652 R DEUTSCH ENGLISH FRAN AIS Sachnr 701764 00 03...

Page 2: ...ures page 21 Operating modes page 22 Installation page 23 Scale drawing page 23 Electrical connection page 25 Programming page 26 Installation and set up operation page 27 Technical information Functi...

Page 3: ...S M M S M S M M S M S M S M M S M M S M M S M M S M M S M M S M RUN M M M M M M M S M M S M M S M M S M S S M Men bersicht Menu structure Structure du menu PF2652 Sachnr 701764 00 3 M S Mode Enter Se...

Page 4: ...values Confirmer la valeur Wert verringern Lassen Sie die Anzeige bis zum maximalen Einstellwert laufen Danach beginnt der Durchlauf wieder beim minimalen Einstellwert Decrease the value Let the disp...

Page 5: ...Druckmedien Bei gasf rmigen Druckmedien ist der Einsatzbereich generell auf max 25bar begrenzt 1 3 stellige Anzeige im Minusbereich XX 0 XX Bei Uni PSI wird 1 10 des PSI Werts angezeigt 7 Segment Anz...

Page 6: ...Schon bei kurzzeitiger berschreitung des Berstdrucks kann das Ger t zerst rt werden Verletzungsgefahr 6 Bestimmungsgem e Verwendung p schaltend PnP Ausgang 1 Ausgang 2 Schaltlogik gilt f r beide Schal...

Page 7: ...ruck auf die Taste Mode Enter bl ttert durch die Parameter Kurzer Druck auf die Taste Set zeigt 15s lang den zugeh rigen Parameterwert Nach weiteren 15s geht das Ger t zur ck in den Run Modus Programm...

Page 8: ...Schraubenschl ssel fest Anzugsdrehmoment 20Nm Das Geh use A ist drehbar Durch G1 Proze adapter ist der Sensor adaptierbar an unterschied liche Proze anschl sse G1 Proze adapter sind gesondert als Zub...

Page 9: ...r langzeitstabile Dichtwirkung der metallischen Abdichtung besteht nur f r einmalige Montage Montage des Adapters Schritt 1 Schrauben Sie den Sensor in den Adapter ein Schritt 2 Spannen Sie Sensor Ada...

Page 10: ...age spannungsfrei und schlie en Sie das Ger t folgenderma en an 10 Adernfarben bei ifm Kabeldosen 1 BN braun 2 WH wei 3 BU blau 4 BK schwarz L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 2 x p schaltend L L 3...

Page 11: ...nuierlich durch Festhalten der Taste Dr cken Sie kurz die Taste Mode Enter Best tigung Der Parameter wird erneut ange zeigt der neue Parameterwert ist wirksam 2 3 4 Weitere Parameter ver ndern Beginne...

Page 12: ...Ver nderung des Schaltpunkts wird der R ckschaltpunkt mitgezogen der Abstand zwischen SPx und rPx1 bleibt konstant Ist der Abstand gr er als der neue Schaltpunkt wird er automatisch reduziert rPx wird...

Page 13: ...abstand zwischen ASP und AEP 25 des Me bereichsendwerts Skalierfaktor 4 AEP ist nur aktiv wenn OU2 I oder U Konfiguration f r Ausgang 2 Es sind 4 Schaltfunktionen und 2 Analogsignale einstellbar Hno H...

Page 14: ...s Me bereichsendwerts Zur cksetzen der Kalibrierdaten Calibration reset Setzt die mit COF eingestellte Kalibrierung zur ck auf Werkseinstellung Dr cken Sie die Mode Enter Taste bis CAr angezeigt wird...

Page 15: ...d2 Me wertaktualisierung alle 200ms d3 Me wertaktualisierung alle 600ms Die Me wertaktualisierung betrifft nur die Anzeige Sie wirkt nicht auf die Ausg nge Ph kurzeitig festgehaltene Anzeige von Druck...

Page 16: ...rten Gutbereichs Bewegt sich der Systemdruck zwischen Schaltpunkt SPx und R ckschaltpunkt rPx ist der Ausgang durchgeschaltet Fensterfunktion Schlie er bzw ge ffnet Fensterfunktion ffner Die Breite de...

Page 17: ...ignalisiert Systemdruck oberhalb des Me bereichs Ausgangssignal 10V I mA P 4 20 MEW AEP 0 ASP 1 I mA P 4 20 AEP ASP 1 0 MEW Werkseinstellung Me bereich skaliert MEW Me bereichsendwert Im eingestellten...

Page 18: ...bei Temperaturschwankungen 10K 0 1 Langzeitstabilit t in der Spanne pro Jahr 0 1 Temperaturkoeffizienten TK im kompensierten Temperaturbereich 0 80 C in der Spanne pro 10 K Gr ter TK des Nullpunkts 0...

Page 19: ...e measured For gaseous media the application is limited to max 25bar 1 3 digit display in the minus range XX 0 XX When Uni PSI 1 10 of the PSI value is displayed Mode Enter Set 2 1 4 3 Controls and in...

Page 20: ...pressure is exceeded only for a short time the unit can be destroyed danger of injuries 21 ENGLISH Function and features p switching PnP Output 1 Output 2 Output polarity applies to both switching out...

Page 21: ...as if in Run mode The parameter names are scrolled with each pressing of the Mode Enter button When the Set button is pressed briefly the corresponding para meter value is displayed for 15s After ano...

Page 22: ...2 Tighten the sensor with a spanner Tightening torque 20Nm The housing A is freely rotat able The unit is adaptable for various G1 process fittings G1 adapters to be ordered separately as acces sories...

Page 23: ...ar B NOTE A guarantee for a long term stable sealing of the metal seal is only valid for once only mounting Mounting of the adapter Step 1 Screw the sensor into the adapter Step 2 Clamp sensor and ada...

Page 24: ...wer before connecting the unit as follows 25 ENGLISH Electrical connection Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 2 x p switching...

Page 25: ...ing briefly or scrolling by holding pressed Press the Mode Enter button briefly acknowledgement The parameter is displayed again the set parameter value becomes effective 2 3 4 Change more parameters...

Page 26: ...pper limit value at which the output changes its switching status SP2 is active only if OU2 Hno Hnc Fno or Fnc Switch off point 1 2 Lower limit value at which the output changes its switching status r...

Page 27: ...vided Minimum distance between ASP and AEP 25 scaling factor 4 AEP is active only if OU2 I or U Configuration of output 2 4 switching functions and 2 analogue signals can be set Hno hysteresis normall...

Page 28: ...f 0 1 of the value of the measuring range Calibration reset Resets the calibration set by COF to the value set at the factory Press the Mode Enter button until CAr is displayed Press the Set button an...

Page 29: ...200ms d3 update of the measured value every 600ms The update interval only refers to the display It has no effect on the outputs ph display of the measured peak value remains for a short time peak ho...

Page 30: ...nge When the sys tem pressure varies between the switch on point SPx and the switch off point rPx the output is switched window function NO or not switched window function NC The width of the window c...

Page 31: ...ated System pressure above the measuring range output signal 10V I mA P 4 20 MEW AEP 0 ASP 1 I mA P 4 20 AEP ASP 1 0 MEW Factory preset Measuring range scaled MEW final value of the measuring range Th...

Page 32: ...re fluctuations 10K 0 1 Long time stability in of the span per year 0 1 Temperature coefficients TEMPCO in the compensated temperature range 0 80 C in of the span per 10 K Greatest TEMPCO of the zero...

Page 33: ...luides gazeux sous pression l emploi est toujours limit 25bar maximum 1 Affichage 3 digits pour les valeurs n gatives XX 0 XX Si Uni PSI 1 10 de la valeur PSI est affich Mode Enter Set 2 1 4 3 El ment...

Page 34: ...m M me si la pression d clatement est d pass e bri vement l ap pareil peut tre d truit danger de blessures 35 FRAN AIS 35 Fonctionnement et caract ristiques sortie positive PnP Sortie 1 Sortie 2 Type...

Page 35: ...nt les param tres sont parcourus Si le bouton poussoir Set est appuy bri vement la valeur de param tre correspondante est indiqu e pendant 15s Apr s 15s suppl mentaires l appareil se remet en mode RUN...

Page 36: ...ocess G1 2 Serrez le capteur Couple de serrage maxi 20Nm Le bo tier A est orientable L appareil est adaptable diff rents types de raccords process Adaptateurs G1 commander s par ment comme accessoires...

Page 37: ...Une garantie pour un effet d tanch it stable long terme du joint m tallique est seulement assum e pour l appareil mont une seule fois Montage de l adaptateur Pas 1 Visser le capteur dans l adapta teu...

Page 38: ...nt de raccorder l appareil comme suit 39 FRAN AIS Raccordement lectrique Couleurs des fils conducteurs des connecteurs femelles ifm 1 BN brun 2 WH blanc 3 BU bleu 4 BK noir L L 3 4 2 1 BU BK WH BN 2 O...

Page 39: ...tre actuelle clignote pendant 5s apr s la valeur est incr ment e pas pas en appuyant sur le bouton poussoir plusieurs fois ou continuellement en le maintenant appuy Appuyer bri vement sur le bouton M...

Page 40: ...igne haut 1 2 Seuil auquel la sortie change son tat de commutation SP2 est actif seul si OU2 Hno Hnc Fno ou Fnc Point de consigne bas 1 2 Seuil auquel la sortie change son tat de commutation rPx est t...

Page 41: ...e dont le signal de sortie est 20mA 10V Ecart minimum entre ASP et AEP 25 AEP est actif seul si OU2 I ou U Configuration pour la sortie 2 4 fonctions de commutation et 2 signaux analogiques peuvent t...

Page 42: ...pas de 0 1 de la valeur de l tendue de mesure Remise 0 du calibrage Calibration reset Remet le calibrage r gl par COF 0 r glage usine Appuyer sur le bouton Mode Enter jusqu ce que CAr soit affich Appu...

Page 43: ...e toutes les 200ms d3 actualisation de la valeur mesur e toutes les 600ms L actualisation ne change que l intervalle d actualisation de l affichage Il n a aucun effet sur les sorties Ph affichage du p...

Page 44: ...pression du circuit est entre la consigne haute SPx et la consigne basse rPx la sortie est commut e fonction fen tre normalement ouvert ou non commut e fonc tion fen tre normalement ferm La largeur de...

Page 45: ...ssion sup rieur l tendue de mesure signal de sortie 10V I mA P 4 20 MEW AEP 0 ASP 1 I mA P 4 20 AEP ASP 1 0 MEW R glage effectu en usine Etendue de mesure avec ajustage d chelle MEW valeur finale de l...

Page 46: ...t avec des fluctuations de temp rature 10K 0 1 Stabilit long terme en du gain par an 0 1 Coefficients de temp rature CT dans la plage de temp rature compens e 0 80 C en du gain par 10 K Meilleur CT du...