Installation instructions
Airflow monitor
SL5105
80007358 / 00 05 / 2016
UK
Page 1: ...Installation instructions Airflow monitor SL5105 80007358 00 05 2016 UK ...
Page 2: ...he cables efficiently against damage Mount the airflow monitor using the supplied mounting clamp Diameter of the mounting hole for the unit 24 mm Use the supplied seal for a hermetically sealed installation Install the unit so that the sensor head is completely inserted into the airflow Position the sensor head in the area of the highest flow velocity Depth of immersion min 32 mm max 120 mm min 32...
Page 3: ...ustment setting potentiometer sensitivity LEDs 1 Switch on the power supply Let the normal flow circulate in the installation preset value and keep it constant 2 When the red LED is lit Turn the potentiometer slowly clockwise until the red LED goes out and the green LED comes on When the green LED is lit Turn the potentiometer slowly anti clockwise until the green LED goes out and the red LED come...