39
UK
8.4.3 Fault diagnosis
In case of a fault switch the safety relay off and on again!
LED display
Cause of the fault
Troubleshooting
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
No voltage supply
•
Overvoltage
•
Connection A1/A3 or A1/A2
reversed
►
Check wiring
►
Check power supply
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
Wire break
•
Feedback contacts open
•
Time-dependent contacts
►
Check wiring
►
Switch the safety relay off
and on again
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
When voltage is applied:
Feedback contacts open
►
Check output circuit
►
Check feedback contacts
►
Exchange external contactor
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
Wiring fault
• Missing link Y4/Y5
•
Short circuit
•
Contacts closed when voltage
is applied
►
Check wiring
►
Open contacts and RESET
or voltage failure
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
Connection A2/A3 reversed
►
Check wiring
K1
E1
T1
POWER
K2
E2
Fault
T
Fault
•
Overvoltage
•
Undervoltage
►
Check wiring
►
Check power supply
K1
E1
T1
POWER
K2
E2
Fault
T
Faul
t
•
Overvoltage
•
Undervoltage
►
Check wiring
►
Check power supply
Summary of Contents for efector 110 G1502S
Page 52: ...52...