ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
400
12.8.35
Acyclic command 105 (69hex) – read device features
5907
Request from fieldbus master to device
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
UID
command request = 65
hex
2
reserved = 0
command number = 105
dec
= 69
hex
3...19
not used
not used
Legend:
UID
user ID
1 byte
00…FF
hex
= 0…255
dec
Response from device to fieldbus master
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
Command status (
→
page
) = 6F
hex
2
reserved = 0
reflected command number
3
2M
DP
EN
reserved = 0
Mod **)
4
reserved = 0
AT
5
reserved = 0
flash memory type
6
hardware
version
7
RTS firmware version number
8
RTS firmware release number
9
AS-i master 1 firmware version number
10
AS-i master 1 firmware release number
11
AS-i master 2 firmware version number
12
AS-i master 2 firmware release number
13
Linux kernel version
14
Linux ramdisk version
15...19
not changed*)
not changed*)
Legend:
2M
2 AS-i master
1 bit
0 = unit has 1 AS-i master
1 = unit has 2 AS-i masters
DP
Profibus DP
1 bit
0 = fieldbus interface Profibus DP not available
1 = fieldbus interface Profibus DP available
EN
Ethernet
1 bit
0 = Ethernet programming interface not available
1 = Ethernet programming interface available
Mod
PLC mode
1 byte
0000 0001
bin
= 01
dec
= PLC in RUN
0000 0010
bin
= 02
dec
= PLC in STOP
0000 0100
bin
= 04
dec
= PLC stops at the breakpoint
0000 1000
bin
= 08
dec
= gateway mode