DP module 7: Command channel
Module 7, command 11dec (0Bhex):
read LPS (list of projected slaves)
8-13
8.12
Module 7, command 11
dec
(0B
hex
):
read LPS (list of projected slaves)
The 2 feedback bytes can only give information about max. 16 slaves. Therefore the slaves are
divided into 4 groups (
→
table page
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
0B
hex
X = slave type (0…1)
0 = standard / A slave
1 = B slave
2
MM X
SSSSS
SSSSS = slave no. (0…31
dec
)
3
0
not used *)
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
0B
hex
2
copy of the request
D6 = command code
D7 = error code
→
page
, table at the bottom
3
→
4
→
provides the addresses of the projected slaves in this
address group
Example: Read LPS (list of projected slaves) of slave group 2 on AS-i master 1
Request of DP master
Byte no.
Value [hex]
Description
1
0B
0B = command 11
2 54
(slave no.
20
)
→
group 2
+ (master no.
1 * 64
)
+ (32, if B slave)
= 84
dec
=
54
hex
3
00
not used *)
4
00
not used *)
Response from controllere
Byte no.
Value [hex]
Description
1
0B
copy of the request
2
54
copy of the request
3
02
hex
=
00000010
bin
→
table page
group 2:
slave 26(A) is projected
4
FE
hex
=
11111110
bin
→
table page
group 2:
slaves 17(A) to 23(A) are projected
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...