ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
The fieldbus command channel (module 11)
Module 11, command 4 – read projected slave configuration
97
6.4.3
Example: read projected slave configuration of slave 16(A)
on AS-i master 1
4745
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 5004
(slave no.
16
)
+ (master no.
1 * 64
)
+ (32, if B slave)
= 80
dec
=
50
hex
04 = command 4
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1 5004
copy of the request
command processed, no error occurred
2 37EF
3 = ID code
7 = IO configuration
E = extended ID code 2
F = extended ID code 1
(corresponds to slave profile S 7.3.E = analogue input module with 4 inputs)