ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
The fieldbus command channel (module 11)
Module 11, command 3 – read current slave configuration
95
6.3.3
Example: Read current slave configuration of slave 7B on
AS-i master 1
4741
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 6703
(slave
no.
7
)
+ (master no.
1 * 64
)
+ (
32
, if B slave)
= 103
dec
=
67
hex
03 = command 3
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1
6703
copy of the request
command processed, no error occurred
2
03EF
0 = ID code
3 = IO configuration
E = extended ID code 2
F = extended ID code 1
(corresponds to slave profile S 3.0.E = 2I/2O module with peripheral fault detection)