The fieldbus command channel (module 11)
Module 11, command 19dec (13hex) – project all
121
6.16.3
Example: project all on AS-i master 1
4796
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 4013
(master no.
1 * 64
)
= 64
dec
=
40
hex
13 = command 19
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1 4013
copy of the request
command processed, no error occurred
2 0080
80
hex
= status: process completed