ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
The fieldbus command channel (module 11)
Module 11, command 6 – read slave parameters
101
6.6.3
Example: read slave parameters of slave 2(A) on AS-i
master 1
4753
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 4206
(slave no.
2
)
+ (master no.
1 * 64
)
+ (32, if B slave)
= 66
dec
=
42
hex
06 = command 6
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1 4206
copy of the request
command processed, no error occurred
2 0F03
0F = current parameter
03 = projected parameter