ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Programming
Overview PLC addresses
153
12.6.2
IEC addresses in the PLC of the controllere
For the digital slave inputs and outputs
% I
B
1.
7
% Q X
1
2
. 2
.3
Data area
Type of
access
Identification
Slave address
Data bit
I = input
Q = output
B = byte
X = bit
1 = S/A slave on master 1
2 = S/A slave on master 2
11 = B slave on master 1
1
2
= B slave on master 2
1 = slave 1
2 = slave 2
…
31 = slave 31
If type of access = X:
0
=
D0
1
=
D1
2
=
D2
3 = D3
S/A slave = single slave or A slave
For the analogue slave inputs and outputs
% I
W 21. 6
.0
% Q W 22. 9
.3
Data area
Type of
access
Identification
Slave address
Data channel
I = input
Q = output
W = word
21 = master 1
22 = master 2
1 = slave 1
2 = slave 2
…
31 = slave 31
0 =
1st channel S/A slave
1 =
2nd channel S/A slave
2 =
3rd channel single slave or:
1st channel B slave
3 =
4th channel single slave or:
2nd channel B slave
4 =
status
S/A slave = single slave or A slave
A/B slaves have max. 2 analogue channels
Status information of analogue slaves
Word
no.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
analogue data channel 0 from/to slave 1 or:
analogue data channel 0 from/to slave -A
1
analogue data channel 1 from/to slave 1 or:
analogue data channel 1 from/to slave 1A
2
analogue data channel 2 from/to slave 1 or:
analogue data channel 0 from/to slave 1B
3
analogue data channel 3 from/to slave 1 or:
analogue data channel 1 from/to slave 1B
4
TIB
TOB
TIA
TOA
TVB
OVB
TVA
OVA
O3
V3
O2
V2
O1
V1
O0
V0
5
analogue data channel 0 from/to slave 2 or:
analogue data channel 0 from/to slave 2A
6
analogue data channel 1 from/to slave 2 or:
analogue data channel 1 from/to slave 2A
7
analogue data channel 2 from/to slave 2 or:
analogue data channel 0 from/to slave 2B
8
analogue data channel 3 from/to slave 2 or:
analogue data channel 1 from/to slave 2B
9
TIB
TOB
TIA
TOA
TVB
OVB
TVA
OVA
O3
V3
O2
V2
O1
V1
O0
V0