8. Test mode
In the test mode the switching behaviour of the monitor can be checked, set and
stored offline. The monitor runs through a freely definable frequency range and
switches the outputs according to the selected switching function and switch
points.
Activate/terminate the test mode
For activation apply the operating voltage and press the
button at the same
time. The display indicates "TST".
In addition to the system and application parameters (starting on page 28) the test
parameters SW, TS and TP are available. The test mode is terminated when the
unit is switched off.
Test parameters
SWx
Sweep on input 1/2
Change of speed of the test frequency
• Values: 1...5 (1 = fast, 5 = slow)
• Default value: 1
TSx
Test Start on input 1/2
Initial value of the test frequency
• Values: 1...60,000 RPM or 0.1...1,000 Hz
• Default value: TS1 = 500 RPM; TS2 = 1000 RPM
TPx
Test Stop on input 1/2
Final value of the test frequency
• Values: 1...60,000 RPM or 0.1...1,000 Hz
• Default value: TS1 = 1500 RPM; TS2 = 1000 RPM
MONITOR
FS-1 / FS-1N
PAGE
34
TSx
TPx
SW1
TS1
TP1
SW2
TS2
TP2
RUN
test
mode
test
frequency
[RPM/Hz]
slip
[%]
RUN
test mode
Parameter range
test mode