Relay plug (2 NC)
DP1613
9
2
2
1
1
3
OUT1
IN1
L1 / L+
L
L+
4
4
IN2
OUT2
4
3
2
1
3
1
2
4
5
1
Fig. 6: Circuits
1:
Always use the provided connection cables to connect other devices.
Information on matching Y cables, Y splitters and other accessories at
5.3.1 Mounting the connector
The threaded connections in the device correspond to the M12 standard. To ensure compliance with
the specified protection rating, only cables that comply with this standard may be used. In the case of
self-assembled cables, the system manufacturer is responsible for the protection rating.
u
Use connectors with gold-plated contacts.
u
During installation, place the connectors vertically so that the coupling nut will not damage the
thread.
u
Observe the coding of the connectors during installation.
If connector in the device:
u
Tighten the cable sockets according to the torque specifications indicated by the cable
manufacturer. Maximum permissible tightening torque: 1.3 ± 0.1 Nm
If sockets in the device:
u
Tighten the cable plug using 1.8 ± 0.1 Nm.
u
Provide all outgoing cables with suitable strain relief after a maximum of 200 mm. Observe the
minimum bending radius of the cables (
Ò
information from the cable manufacturer).
Maximum cable length: 30 m on each side
5.3.2 Removing the connector with vibration protection
u
Press the connector against the unit and simultaneously loosen the coupling nut.