DN1042 Installation Manual

Product Description

The DN1042 is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV/ES1 output voltage.

Intended Use

This device is designed for Installation in an enclosure and is intended for commercial use, such as
in industrial control, process control, monitoring, measurement, Audio/Video, information or
communication equipment or the like. Do not use this device in equipment where malfunction may
cause severe personal injury or threaten human life.
If this device is used in a manner outside of its specification, the protection provided by the device
may be impaired.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter),
the device is not suited to supply a local DC power network in industrial, residential, commercial and
light-industrial environments.
Do not use this device on AC 200V mains with more than 4.5A load when the application is sensitive
to short output voltage dips during mains interruptions even with a length shorter than 20ms.

Installation Instructions

Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up
to +45°C, 75°C for ambient temperatures up to +55°C and 90°C for ambient temperatures up to
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. Unused screw
terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage
between the input terminal and the PE potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left
and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the
device is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 20A without additional
protection device. For higher branch circuits use an additional protection device. If an external input
protection device is utilized, do not use one smaller than a 10A B- or 6A C-characteristic to avoid a
nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.

Functional Description

The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive and capacitive loads. If capacitors with a capacitance >10mF and
2.5A or >5mF with 5A additional current load are connected, the unit might charge the capacitor in
an intermittent mode. No limitation in combination with an additional resistive type of load.
Do not apply return voltages from the load to the output terminals higher than 35V.
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit.
The green DC-OK LED reports an output voltage above 18V of a running device.
At heavy overloads (when output voltage falls below 2...10V, depending on input voltage), the
device delivers continuous output current for 30ms. After this, the output is switched off for 160ms
before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists.
Do not parallel devices for higher output currents.
Same devices can be connected in series for higher output voltages. It is allowed to connect as
many outputs in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 34V. The
output shuts down. To attempt a restart, turn the input power off for at least 90s.

Technical Data

All values are typical figures specified at 230Vac, 50Hz input
voltage, 24V 5A output load, 25°C ambient temperature and after
a 5 minutes run-in time unless otherwise noted.

Output voltage

DC 24V

Nominal

Adjustment range

24 – 28Vdc

Factory setting 24.1V

Output current

5.0 – 4.3A

Below +55°C ambient

3.1 – 2.7A

At +70°C ambient

Derate linearly b55°C and +70°C

Input voltage AC

AC 200 – 240V 

±10%

Mains frequency

50 – 60Hz

±6%

Input current AC

1.06A

Power factor

0.54

Input inrush current

28A pk

At 40°C, cold start

Efficiency

90.5%

Power losses

12.6W

Hold-up time

33ms

Temperature range

-10 to +70°C

Max. wire size (litz wire)

4mm²

For all terminals

Wire size AWG

AWG 20-10

For all terminals

Max. wire diameter

2.8mm

For all terminals

Wire stripping length

7mm / 0.28inch 

For all terminals

Tightening torque

1Nm / 9lb.inch

For all terminals

Size

(wxhxd)

39x124x124mm 

Without DIN-rail

Weight

350g / 0.77lb

Functional Diagram

+

+

-
-

Output

Over-

Voltage

Protection

Input Rectifier

Inrush Current

Limiter

Voltage

Regulator

Power

Converter

Output

Filter

Input Fuse
Input Filter

V

OUT

L

N

DC-OK

LED

Output Characteristic

Output voltage

10A

24V

Output current

0V

1A

2A

3A

5A

0A

Adjustment range

28V

4A

6A

7A

9A

8A

A: intermittent current 264Vac
B: intermittent current 187Vac

A

B

Temperature Range

Allowed output current at 24V

Ambient temperature

0A

-10

5.0A

0

+70°C

3.1A

+55