AL4002
Remote I/O module 16 DI
64
11.2.3 Acyclical data
11.2.3.1 Data record: Filter configuration
Index
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
Port
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Pin
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
Per index:
Byte (off-
set)
Bit
7
6
5
4
3
2
1
0
0…1
Debounce Time
2…3
Hold Time
4
res.
res.
res.
res.
res.
res.
Hold Level
Input Invert-
er
Legend:
• Debounce Time
Debounce time (= value * 0.1 ms)
Debounce Time = 0x0123:
• Debounce time[0] = 0x01
• Debounce time[1] = 0x23
UINT16 / rc
• 0x0000: 0 ms
…
• 0x01F4: 50 ms
• Hold Time
Hold time (= value * 0.1 ms)
Hold Time = 0x1234:
• Hold time[0] = 0x12
• Hold time[1] = 0x34
UINT16 / rc
• 0x0000: 0 ms
…
• 0xEA60: 6000 ms
• Input Inverter
Inversion
1 bit / rc
• 0x0: do not invert
• 0x1: invert
• Hold Level
Hold level
1 bit / rc
• 0x0: hold LOW
• 0x1: hold HIGH