IO-Link Master with EtherCAT Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
93
>
Diagnostics Data (0xA000)
33821
The device provides the following diagnostic data for each port:
Selection of the IO-Link port via n (n = 0: port X01, n = 1: port X02,...)
Index
Sub-
index
Description
Possible values
Data type /
Access
0xA0n0
Diagnostics Data
0x01 IO-Link State
0x00:
INACTIVE
UINT8 / r
0x01:
DIGINPUT
0x02:
DIGOUTPUT
0x08:
OPERATE
0x09:
STOP
0x02
Subindex 0x02: Lost Frames
UINT8 / r
r ... read only
>
Device Status / Port Status (0xF000)
33812
Status of the IO-Link device at the port X01...X08
Selection of the IO-Link port via n (n = 0: port X01, n = 1: port X02,...)
Index
Sub-
index
Description
Possible values
Data type /
Access
0xF000
Module Device Profile
0x01
Module Index Distance
0x0010
UINT16 / r
0x02
Maximum number of modules
0x0008
UINT16 / r
0xF030
Configured Module Ident List
0xF050
Detected Module Ident List
0xF100
Device Status
UINT8 / r
0x01
IO-Link Port X01
→
Mapping: Device Status (0xF100)
(
→ S.
...
...
0x0n
IO-Link Port X08
0xF101
IO-Link Port Qualifier
UINT8 / r
0x01
PQI Port X01
→
Mapping: Port Qualifier (0xF101)
(
→ S.
...
...
0x0n
PQI Port X08
r ... read only