IO-Link Master with PROFINET Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
66
>
9.3.5
Configure IO-Link devices
52482
The AL1302 supports the configuration of the connected IO-Link devices via the PROFINET
application. The configurable parameters depend on the IO-Link device that is used.
Configurable parameters of the IO-Link devices:
→ IO Device Description (IODD) of the
IO-Link Devices
The following options are available:
Symbol (function block)
Description
Notes
IO_LINK_DEVICE (FB5001) Acyclic access to the
parameters of an IO-Link
device
Input parameter:
CAP: Access point for function
AL1302: AL1302: 0xB400
PORT: Slot/sub-slot of the IO-Link interface of the connected
IO-Link device
Port X01: 1
Port X02: 2
...
Port X08: 8
IOL_INDEX and IOL_SUBINDEX: Index and sub-index of
the parameter (depends on the IO-Link device:
→ IO Device
Description (IODD))
IOL_CALL (FB1)
Acyclic access to the
parameters of an IO-Link
devices (obsolete)
→ IO_LINK_DEVICE (FB5001)