IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
68
>
Mapping: PQI
34393
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnosis
present
Wrong PD
Output Length
Wrong PD
Input Length
Wrong
Cycle Time
Wrong
VID / DID
Invalid Data
Bit
Dev Not Conn
IOL Mode
reserved
Legend:
[IOL Mode]
Operating mode of the IO-Link port
1 bit
0x0
not IO-Link
0x1
IO-Link
[Dev Not Conn]
Connection between IO-Link Device and IO-Link port
1 bit
0x0
connected
0x1
not connected
[Invalid Data]
Status of the process input data on the IO-Link port
1 bit
0x0
valid Data
0x1
invalid Data
[Wrong VID/DID] Evaluation, whether actual and projected Vendor ID
and Device ID match
1 bit
0x0
OK
0x1
wrong VID and/or DID
[Wrong Cycle
Time]
Evaluation, whether actual and projected cycle time
match
1 bit
0x0
OK
0x1
wrong cycle time
[Wrong PD Input
Length]
Evaluation, whether actual and projected input process
data length match
1 bit
0x0
OK
0x1
projected length too small
[Wrong PD
Output Length]
Evaluation, whether actal and projected output process
data length match
1 bit
0x0
OK
0x1
projected length too small
[Diagnosis
present]
Signals a new diagnosis event (Coming Event, Single
Shot Event)
Coming Events are removed when if the related
Disappearing Event appears
Single Shot Events are removed automatically
1 Bit
0x0
no event
0x1
New event present