49
ifm
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 69K (AL1101)
2017-05-31
Configuration
>
8.5
Profinet: Configure IO-Link devices
18428
The AL1101 supports the configuration of the connected IO-Link devices out of the Profinet projection
software. The configurable parameters depend on the corresponding IO-Link device.
Information about the usable functions:
→
Profinet: Programmers' notes
(
Available parameters of the IO-Link devices:
→ Operating instructions of the IO-Link device
>
8.6
Profinet: Programmers' notes
12761
The programmer can access on the following data from the PLC application:
Read device information of the AL1101
Read diagnostics and alarms
Set parameters of the connected IO-Link devices
The following sections show the available options.
Further information about the functional/operational blocks:
→ Help function of the Profinet
projection software
>
8.6.1
Read and write I&M datasets
2261
Symbol / function
block
Meaning
Remarks
GET_IM_DATA / FB
Function block for reading the I&M datasets of
a device
GET_IM_DATA only supports the reading
of the I&M0 dataset
Input parameters:
IM_TYPE = 0
RDREC
Function block for acyclic reading of datasets
Input parameters:
I&M0: Index = 0xAFF0
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
WRREC
Function block for acyclic writing of datasets
Observe access rights on datasets!
Input parameters:
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3