IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
60
>
Mapping: PQI
52019
Bit
7
6
5
4
3
2
1
0
PQ
DE
DA
DACT
res.
res.
DI (Pin 2)
DI (Pin 4)
Legend:
DI (Pin 4) Signal level of the digital input on pin 4 (if in use)
1 bit
0x0
LOW
0x1
HIGH
DI (Pin 2) Signal level of the digital input on pin 2 (DI)
1 bit
0x0
LOW
0x1
HIGH
DACT
Device Deactivated: indicates whether IO-Link device
has been deactivated via the port function
1 bit
0x0
IO-Link device activated
0x1
IO-Link device deactivated
DA
Device Available: indicates whether an IO-Link device
is available at the IO-Link port
1 bit
0x0
no IO-Link device available
0x1
IO-Link device recognised and
in the operating mode
"Peroperate" or "Operate"
DE
Device Error: indicates occurring errors in the
connected IO-Link device
1 bit
0x0
no error
0x1
error or warning
PQ
Port Qualifier: indicates whether the input data / output
data of the IO-Link device are valid
1 bit
0x0
Data is invalid
0x1
Data is valid