background image

Passive power distributor

AC5050 AC5051

7

5 Electrical connection

The device must be connected by a qualified electrician.

Observe the national and international regulations for the installation of electrical equipment.

Disconnect power.

Voltage supply according to SELV / PELV.

The IP rating of the overall system depends on the protection ratings of the individual devices, the
applied connection elements and the corresponding protective caps.

The M12 connection parts in the device comply with the ingress resistance requirements of the
standard EN61076-2-101. To adhere to the protection rating, only cables certified to this standard
must be used. The system architect undertakes to ensure the ingress resistance of cables they have
cut to length.

Recommended maximum cable length: 5 m (AS-i operation)

Recommended maximum cable length: 20 m (IO-Link operation)

Fasten the cable with a tightening torque of 0.6...0.8 Nm, observe the cable manufacturer's
specifications.

u

Carry out the fitting according to the indications of the cable manufacturer, a max. tightening torque
of 0.8 Nm is permissible.

u

During installation, place the M12 connector vertically so that the coupling nut will not damage the
thread.

u

Provide cables with a strain relief depending on the mounting conditions to avoid excessive strain
on the installation points and the M12 connections.

u

Ensure correct fit and proper assembly of the M12 connection parts. If these instructions are not
complied with, the specified protection rating cannot be guaranteed.

u

To connect the device, use M12 connectors with protection rating IP 65 / IP 66 / IP 67 or higher,
depending on the requirements of the application.

u

Use M12 connectors with gold-plated contacts.

u

Cover the unused sockets with M12 protective caps, tightening torque 0.6...0.8 Nm.

In case of cables that are longer than 20 m (IO-Link operation), take the voltage drop and the
necessary minimum supply voltage of 20 V into consideration.

5.1 UL applications

To connect devices, only use UL-certified cables belonging to category CYJV or PVVA with a
minimum temperature of 80 °C (75 °C in case of a maximum ambient temperature of 40 °C).

5.2 Wiring

Voltage supply Power IN 0 (voltage input)

IO-Link operation

M12 connector

(4 poles, A-coded)

AS-i operation

1: + 24 V DC (US)

4

3

2

1

1: AS-i +

2: GND (UA)

2: AUX -

3: GND (US)

3: AS-i -

4: + 24 V DC (UA)

4: AUX +

Summary of Contents for AC5050

Page 1: ...Operating instructions Passive power distributor AC5050 AC5051 11480272 01 12 2022 GB ...

Page 2: ...ngs used 3 2 Safety instructions 4 3 Intended use 5 3 1 Safety symbol on the device 5 4 Installation 6 4 1 Install device 6 5 Electrical connection 7 5 1 UL applications 7 5 2 Wiring 7 5 3 Voltage supply fuse 8 6 Operating and display elements 9 7 Scale drawing 10 8 Maintenance repair and disposal 11 ...

Page 3: ...quirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warnings used ATTENTION Warning of damage to property CAUTION Warning of personal injury w Slight reversible injuries may result WARNING Warning of serious personal injury w Death or serious irre...

Page 4: ... before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur In case of malfunctions of...

Page 5: ...current detection no shutdown AC5050 4 port power distributor AC5051 8 port power distributor The device is designed for use without a control cabinet indoor use The impedance of the power distributor corresponds to that of a standard slave in the AS i network u Only use the device within the limits of the technical data 3 1 Safety symbol on the device Safety symbol on the device u Adhere to the o...

Page 6: ... Installation 4 1 Install device u Disconnect the power to the machine during installation u Use a flat mounting surface for installation u Fix the unit to the mounting surface using 2 M5 mounting screws and washers max tightening torque 1 8 Nm ...

Page 7: ...of 0 8 Nm is permissible u During installation place the M12 connector vertically so that the coupling nut will not damage the thread u Provide cables with a strain relief depending on the mounting conditions to avoid excessive strain on the installation points and the M12 connections u Ensure correct fit and proper assembly of the M12 connection parts If these instructions are not complied with t...

Page 8: ... 5 n c 5 n c 5 3 Voltage supply fuse Observe the maximum current rating of the M12 connections tech data ATTENTION No current limitation within the unit w If the M12 connectors are overloaded overcurrent damage to the unit or fire is possible w Each supply connection AS i AUX AS i operation or 24 V DC US 24 V DC UA IO Link operation must be limited to the values of the technical data current consu...

Page 9: ...S AS i LED US AS i LED UA AUX Fig 1 LED assignment LED US AS i green US AS i voltage supply ok LED UA AUX green UA AUX voltage supply ok LED FLT US AS i flashes red US AS i voltage output overloaded overcurrent detected LED FLT UA AUX flashes red UA AUX voltage output overloaded overcurrent detected ...

Page 10: ...050 AC5051 Passive power distributor 10 7 Scale drawing LED M12 M12 38 4 152 136 59 3 5 3 21 Fig 2 AC5050 4 port power distributor 208 192 59 3 5 3 LED M12 M12 38 4 21 Fig 3 AC5051 8 port power distributor ...

Page 11: ...nly the manufacturer is allowed to repair the unit u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations Cleaning the unit u Disconnect the unit from the voltage supply u Clean the unit from dirt using a soft chemically untreated and dry micro fibre cloth ...