
AS-i Gateway with Profinet device interface
160
>
8.7.6
Fieldbus alarms
Content
Process alarms .....................................................................................................................................160
Diagnosis alarms ..................................................................................................................................160
Step7 programmer's notes ...................................................................................................................170
41518
Depending on the compatibility mode currently active the AC1401/02 supports the following diagnosis
/ alarm options.
>
Process alarms
41767
Process alarms are used when a critical value or status occurs during the process in the plant. This
can be the case e.g. when the temperature of a tank is too low or too high.
The process alarms are application-specific. For this reason, the manufacturer does not implement
process alarms in this device.
>
Diagnosis alarms
41449
Diagnosis alarms are used where an error or event occurs in the device.
Examples:
AS-i configuration error
Peripheral fault on an AS-i slave
Slot:
0 (corresponds to the host; in the ifm classic mapping model, this is the AC1401/02)
sub-slot:
1 (others are not supported from some PROFINET-controllers.
Channel
: 0x08000 (fixed, others are not supported)
Channel property:
is always "diagnosis"
Alarm numbers:
are in the "Manufacturer Specific" area (0x0100 and 0x7FFF)
All used alarms are "standard alarms" and use the "Add Channel Diagnosis Request"
function on the Hilscher Alarm API.