10
Explanation of the abbreviations:
SIL
Safety Integrity Level
Safety Integrity Level SIL 1-4 to IEC 61508� The
higher the SIL the lower the probability that a
safety function will fail�
PL
Performance Level
Capability of safety-related parts to perform a
safety function at predictable conditions to fulfil the
expected risk reduction�
PFD
avg
Probability of failure on
demand
PFH
D
Probability of Dangerous
Failure per Hour
T
Life time
Max� service life�
11 Technical data
Electrical design
2 safe inputs / 1 non-safe LED output
Operating voltage
26�5���31�6 V DC
Current consumption
< 50 mA
Inputs
Wiring
DC PNP
Voltage supply
via AS-i
Voltage range
≥ 20 V DC
Short-circuit proof
yes
Input current high/low
4 mA
LED output
Supply via AS-i
yes
Short-circuit proof
no
Integrated watchdog
yes
Max� current load output
10 mA
LED
red
Ambient temperature
-25���60 °C
Protection rating
IP 67
AS-Interface /
extended addressing mode possible version 2�1 / no
AS-i profile
S-7�B�E
I/O configuration
7 [Hex]