8  Additional settings (optional)

8.1  Low flow adjustment

If the unit is used in media other than water, you should additionally adapt the unit 

to the minimum flow� 
Note: The following adjustment must only be carried out after the high flow adjust-

ment�

 

Let the minimum flow circulate in the installation or ensure flow standstill�

 

Press the pushbutton 

 and keep it pressed�

 

> LED 0 lights, after approx� 5 s it flashes�

 

Release the pushbutton� The unit adopts the new value and passes into the 

operating mode�

8.2  Configure the switching output

The unit is delivered as normally open� In case of need you can change the output 

to normally closed:

 

Press the pushbutton 

 for at least 15 s�

 

> LED 0 lights, after approx� 5 s it flashes�

 

> After 10 s the current setting is displayed: LEDs 5���9 light orange (= output 

normally open)�

 

> After approx� 15 s LEDs 0���4 flash orange� 

 

Release the pushbutton� The output is changed to normally closed operation�

For a new changeover repeat the operation�

8.3  Restore the factory setting (reset)

 

Press the pushbutton   for at least 15 s�

 

> LED 9 lights, after approx� 5 s it flashes�

 

> After approx� 15 s LEDs 0���9 flash orange� 

 

Release the pushbutton� All settings are reset to the factory setting:

 -operating area: 5 ���100 cm/s for water

 -switch point: LED 7

 -output function: NO

 -unlocked�

8.4  Lock / unlock the unit

The unit can be locked electronically to prevent unintentional settings�

Summary of Contents for SI0562

Page 1: ...Operating instructions Flow monitors SI5006 SI0562 704194 04 02 2022 UK...

Page 2: ...stem 6 4 3 Mounting operation 6 5 Electrical connection 7 6 Operating and display elements 8 7 Set up and settings for water 9 7 1 Change the switch point optional 9 7 2 High flow adjustment optional...

Page 3: ...icable for any service personnel authorised by the manufacturer of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable f...

Page 4: ...case of need you can change the output to normally closed 8 2 It then applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reache...

Page 5: ...lation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pi...

Page 6: ...rces of interference 4 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the thread...

Page 7: ...ast acting The permissible potential difference between supply and output circuit is max 300 V The metal parts of the housing must be properly grounded For this you can for example attach a grounding...

Page 8: ...For information about available sockets go to www ifm com 6 Operating and display elements 1 Operation display The green LEDs indicate the current flow the LEDs 0 to 9 represent the range between no...

Page 9: ...ur normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 7 2 You can restore the factory setting any time 8 3 7 1 Change the switch point optional Fo...

Page 10: ...en Let the normal flow circulate in the installation Press the pushbutton and keep it pressed LED 9 lights after approx 5 s it flashes Release the pushbutton The unit is now adapted to your flow condi...

Page 11: ...of need you can change the output to normally closed Press the pushbutton for at least 15 s LED 0 lights after approx 5 s it flashes After 10 s the current setting is displayed LEDs 5 9 light orange o...

Page 12: ...then passes into the operating mode with unchanged values Possible cause aid Error during installation Read chapter 4 Installation Check whether all requirements have been met The difference between...

Page 13: ...output closed LED red output open LED 9 flashes current flow above the representation range LED 0 flashes current flow far below the represen tation range Interference indicators Display OFF no LED li...

Reviews: