UK
8.2 Explanation of the menu
SP1/rP1
Maximum / minimum value for system pressure, at which output 1 changes
its switching status�
SP2/rP2
Maximum / minimum value for system pressure, at which output 2 changes
its switching status�
OU1
Output function for OUT1:
• Switching signal for the limit values: hysteresis function [H ��] or window
function [F ��], normally open [� no] or normally closed [� nc] each�
OU2
Output function for OUT2:
• Switching signal for the limit values: hysteresis function [H ��] or window
function [F ��], normally open [� no] or normally closed [� nc] each�
• Analogue signal for the current system pressure: 4���20 mA [I] or 0���10 V
[U]�
ASP
Analogue start point for the system pressure: measured value at which
4 mA / or 0 V are output�
AEP
Analogue end point for the system pressure: measured value at which
20 mA / or 10 V are output�
EF
Extended functions / Opening menu level 2�
HI Maximum value memory for the system pressure�
LO Minimum value memory for the system pressure�
COF Zero point calibration�
CAr Calibration reset�
dS1/dS2 Switch-on delay for für OUT1 / OUT2�
dr1/dr2 Reset delay für OUT1 / OUT2�
P-n Output polarity: pnp / npn
dAP Damping for the switching outputs
dAA Damping for the analogue output
diS Update rate and orientation of the display�
Uni Standard unit of measurement for the system pressure�