4
Processing of the measured signals
4.1
The unit shows the current system pressure on its display�
•
It generates 1 output signal according to the parameter setting�
•
OUT1
switching signal for pressure limit values
Switching function
4.2
OUT1 changes its switching state if it is above or below the set switching limits
(SP1, rP1)� The following switching functions can be selected:
Hysteresis function / normally open: [OU1] = [Hno] (→ fig. 1).
•
Hysteresis function / normally closed: [OU1] = [Hnc] (→ fig. 1).
•
First the set point (SP1) is set, then the reset point (rP1) at the requested distance�
Window function / normally open: [OU1] = [Fno] (→ fig. 2).
•
Window function / normally closed: [OU1] = [Fnc] (→ fig. 2).
•
The width of the window can be set by means of the distance between SP1 and
rP1� SP1 = maximum value, rP1 = minimum value�
�
�
��
��
�
�
�
�
���
���
��
�
�
��
��
�
�
�
�
��
���
���
1
2
P = system pressure; HY = hysteresis; FE = window