34
14.2 Storage tank
Level control and min / max monitoring with 4 switching outputs�
Replaces 4 float switches�
Configuration of the switching outputs 1 ��� 4 (bin = OFF)
SP1
Maximum value exceeded → alarm.
OU1
Hysteresis function, normally closed (Hnc)�
SP2
Upper preset value reached → finish refilling.
OU2
Hysteresis function, normally open (Hno)�
SP3
Below lower preset value → start refilling.
OU3
Hysteresis function, normally closed (Hnc)�
SP4
Below min. value → alarm.
OU4
Hysteresis function, normally open (Hno)�
rP1���
rP4
Each slightly below SPx to suppress wave movements (factory setting)�
t
L
SP1
SP2
1
0
OUT1
Hnc
1
0
OUT2
Hno
SP3
SP4
1
0
OUT3
Hnc
1
0
OUT4
Hno
OFS
XX.X
XX�X = display value