34
10.6 Reset all parameters to factory setting
►
Select [rES], then press [Set] and keep it pressed until [----] is displayed�
►
Briefly press [Mode/Enter]�
> The unit reboots and the factory settings are restored�
Note: On delivery the unit is not operational� First, the basic settings must
be entered → 10.2.
10.7 Changing basic settings
Required after changes to the probe or to the application area�
10.7.1 Re-enter the probe length
►
Change to menu level 2
►
Select [LEnG] and set probe length L�Note the set unit of measurement
(cm or inch)�Step increment: 0�5 cm / 0�2 inch�
Remarks on the determination of the probe length:
► Note the remarks → 6.3.1 (single probes) or → 6.3.3 (coaxial probes).
►
Briefly press [Mode/Enter]�
Note: After changing the probe length, the values for OFS and the switching
limits must also be reviewed / re-entered�
10.7.2 Setting to another medium
►
Select [MEdI] and set the value:
-[HIGH] for water and water-based media�
-[LOW] for oils and oil-based media�
Note: In case of doubt, carry out an application test to ensure the setting
which is best for your medium�
10.7.3 New entering of the type of probe used
►
Select [Prob] and set the value:
-[rod] for single probe�
-[COAX] for coaxial probe�
• The detection of water and water-based media is possible with the single
probe as well as with the coaxial probe�
• The detection of oils and oil-based media is only possible with the coaxial
probe� Therefore, the parameter [Prob] is not available in case of the
setting [MEdI] = [LOW] (the value [COAX] is preset)�