Operating instructions (safety-related part ATEX)

Remarks for safe use in hazardous areas

Functions and features

•  Use in hazardous areas according to the classification

II 3D

 (group II, category 3D, apparatus for dust atmosphere).

The requirements of the standards EN 61241-1 and EN 61241-0 are met. 
Shock test to EN 60947-5-2 with 0.5 joules.

• Marking 

 II 3D Ex tD A22 IP65 T90°C X    Ta: -20...60°C

ID000A / ID500A

Installation / Set-up

The units must only be installed, connected and set up by qualified staff. The qualified staff 
must have knowledge of protection classes, regulations and provisions for apparatus in 
hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable 
for the application.

Installation remarks / Installation

•  Adhere to the relevant national regulations and provisions.
•  The relevant installation regulations must be adhered to.
•  Avoid electrostatic charging on housings and cables.
•  To avoid electrostatic charging steps must be taken to ensure the equalisation of potential 

of metal parts (plug housing, fixing elements, etc.). 

•  Protect the units and the cables efficiently against damage.
•  To avoid soiling, do not remove the dust caps from the cable glands until introducing the 

cables.

•  For units with cable gland: To ensure the required minimum protection, the clamping screw 

of the cable gland must be firmly tightened (see technical data sheet for tightening torque).

•  Maintenance intervals are application-specific and therefore need to be defined by the 

operator depending on the operating conditions. 

•  During maintenance, especially those parts on which the type of protection depends need 

to be examined (e.g. integrity of the components of the cable gland, of the seals).