45
UK
9 Scale drawing
35
,5
25
10
0
LED
105
1: Combicon connector with screw terminals (supplied)
10 Technical data
G1501S
Safety relay with relay outputs
Terminal block Phoenix Contact MSTBO
Meets the requirements of:
EN ISO 13849-1: 2008 category 4 PL e, SIL 3 (IEC 61508), type IIIC (EN 574)
Electrical design
Relay
Output function
2 safety-related NO (floating contacts)
1 signal output (positive switching)
Operating voltage
24 V DC (19�2���30) incl� 5 % residual ripple
Contact rating
6 A, 250 V AC / 24 V DC (min 6 mA)
Short-circuit protection / overload
protection
The contacts are to be protected by means of fuses
with a nominal current of < 3�6 A
Current consumption
< 200 mA
Function display
voltage (green), error (red), output status
(2 x yellow), input (2 x yellow)
Summary of Contents for G1501S
Page 1: ...706199 00 04 2012 Original operating instructions Safety relay with relay outputs G1501S UK ...
Page 16: ...16 Input circuit Output status LED display ...
Page 17: ...17 UK Input circuit Output status LED display ...
Page 26: ...26 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Page 34: ...34 8 4 2 Function Input circuit Output status LED display N O contact activated ...
Page 44: ...44 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Page 49: ...49 UK ...