IFM Electronic Efectorsod PE70 Series Operating Instructions Manual Download Page 3

3

UK

1  Preliminary note

1.1  Symbols used

Instruction

>

Reaction, result

[…] Designation of pushbuttons, buttons or indications

Cross-reference
Important note: 

Non-compliance can result in malfunctions or interference�

2  Safety instructions

• 

Please read this document prior to set-up of the unit� Ensure that the product is 

suitable for your application without any restrictions� 

• 

If the operating instructions or the technical data are not adhered to, personal 

injury and/or damage to property can occur� 

•  Check the compatibility of the product materials (→ chapter 12 Technical data) 

with the media to be measured in all applications� 

• 

Use in gases at pressures > 25 bar only after contacting the manufacturer ifm�

3  Functions and features

The unit monitors the system pressure of machines and plants.

Applications

 

Type of pressure: relative pressure

Order no.

Measuring range

Permissible  

overpressure

Bursting pressure

bar

PSI

bar

PSI

bar

PSI

PE7002

0���100

0���1 450

300

4 350

650

9 400

PE7003

0���25

0���363

150

2 175

350

5 075

PE7004

-1���10

-14�5���145

75

1 087

150

2 175

PE7006

0���2�5

0���36�3

20

290

50

725

PE7007

0���1

0���14�5

10

145

30

450

PE7009

-1���1

-14�5���14�5

20

290

50

725

MPa = bar ÷ 10 / kPa = bar × 100

11  Factory setting �������������������������������������������������������������������������������������������������16

Summary of Contents for Efectorsod PE70 Series

Page 1: ...Operating instructions Pressure sensor PE70xx UK 706182 01 08 2012...

Page 2: ...10 9 2 Configuring the display optional 12 9 3 Setting the output signals 12 9 3 1 Setting of the output function 12 9 3 2 Setting of the switching limits 12 9 4 User settings optional 13 9 4 1 Setti...

Page 3: ...heck the compatibility of the product materials chapter 12 Technical data with the media to be measured in all applications Use in gases at pressures 25 bar only after contacting the manufacturer ifm...

Page 4: ...s inactive in case of a fault The following functions are available via IO Link OUT1 reading the current process value changing the parameters and transferring them to other units of the same type usi...

Page 5: ...utput based on the DESINA specification if OU2 dESI If there is no fault the output is switched and carries UB if P n PnP or UB if P n nPn In case of malfunctions in the following areas the output is...

Page 6: ...t be adhered to Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows 2 x p switching 2 x n switching Pin 1 Ub Pin 3 Ub Pin 4 OUT1 binary switching output pressure monitorin...

Page 7: ...s 5 and 6 not used LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Indication of the current system pressure Indication of the parameters and parameter values 1...

Page 8: ...8 8 Menu 8 1 Menu structure...

Page 9: ...ing signal for the pressure limit values hysteresis function H or window function F either normally open no or normally closed nc Diagnostic signal OU2 dESI EF Extended functions opening of menu level...

Page 10: ...ton once or continuously by keeping the button pressed Numerical values are incremented continuously To reduce the value let the display move to the maximum setting value Then the cycle starts again a...

Page 11: ...program Activate the EF button If menu level 2 is protected by an access code the input field for the code no is activated Enter valid code no Locking unlocking The unit can be locked electronically...

Page 12: ...output function Select OU1 and set the function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally open Fnc window function normally closed Sele...

Page 13: ...the switching status in milliseconds The following fix values can be set they define the switching frequency f of the output dAP 3 6 10 17 30 60 125 250 500 f Hz 170 80 50 30 16 8 4 2 1 9 5 Service fu...

Page 14: ...arameter is displayed Press Set briefly The unit displays the corresponding parameter value for about 15 s After another 15 s the unit returns to the Run mode 10 2 Fault indication OL Overload pressur...

Page 15: ...49 0 01 PE7004 bar 0 90 10 00 0 95 9 95 0 05 PSI 12 145 13 144 1 MPa 0 090 1 000 0 095 0 995 0 005 PE7006 bar 0 02 2 50 0 01 2 49 0 01 PSI 0 4 36 2 0 2 36 0 0 2 kPa 2 250 1 249 1 PE7007 mbar 10 1000...

Page 16: ...1 23 VMR OU1 Hno OU2 Hno SP2 75 VMR rP2 73 VMR dS1 0 0 dr1 0 0 dS2 0 0 dr2 0 0 P n PnP dAP 60 diS d2 Uni bAr mbAr the indicated percentage of the final value of the measuring range VMR of the correspo...

Page 17: ...17 UK...